Point level detection, Liquicap FTI51/52

FTI51

Temperature     : -80 to +200°C

Pressure              : Vacuum to +100bar

Electrode Type  : Rod

Sensor length    : 6m (20ft)6

FTI52

Temperature     : -80 to +200°C

Pressure              : Vacuum to +100bar

Electrode Type`: Cable/Rope

Sensor length    : 12m (39ft)

Advantage

Reliable and safe measurement due to active build-up compensation

Description

Capacitance limit switches for liquids. Suitable for hazardous area use.

Available as both a rope and rod version, Liquicap M offers accurate and reliable level limit detection. It offers a variety of housings, process connections (starting from ½”), certification and approvals, so that you get exactly what you need. Liquicap M offers outstanding performance in storage, buffer and process tanks.

The probe can be used both in vacuums and in overpressure up to 100 bar. The sealing and insulation materials used allow operation in temperatures from -80°C up to 200°C.

Technical Data FTI51 FTI52
Temperature -80 °C … +200 °C -80 °C … +200 °C
Pressure -1 to 100 bar -1 to 100 bar
Output Relay, PNP, 2-wire PFM (FTC325/625) Relay, PNP, 2-wire PFM (FTC325/625)
Ambient temperature (housing) -50°C…+70°C -50°C…+70°C
Protection IP66, IP67, NEMA4X (F15, F16, F17 housing)

IP66, IP68, NEMA4X (F13, T13 and remote housing)

IP66, IP67, NEMA4X (F15, F16, F17 housing)

IP66, IP68, NEMA4X (F13, T13 and remote housing)

Certification ATEX, FM, CSA, CSA C/US, IEC Ex, TIIS, INMETRO, NEPSI, EAC ATEX, FM, CSA, CSA C/US, IEC Ex, TIIS, INMETRO, NEPSI, EAC
Electrodes Rod Type Cable/Rope Type
Process connections Flanges, threads, special hygienic process connections Flanges, threads, special hygienic process connections
Reproducibility 0.1% 0.1%

For more information, specific application advice or to order,

Please Contact us on +91 8367005552 or +91 9063008734

email: info@sigmaautomation.co.in or instsales@sigmaautomation.co.in

Technical Information

FTI51/52

TI For FTI51_52